Process equipment for erection and maintenance of power transformers, reactors and other oil-filled equipment with voltage up to 1150 kV including
JSC «PDTB «ELEKTROTECHMONTAZH»
Ukraine, Kharkov

Plants for degassing, nitriding, drying, heating and filtering transformer oils

EAC

The equipment complies with the requirements of technical regulations of the Customs union TR CU 010/2011 "On the safety of machinery and equipment" and TR CU 004/2011 "On the safety of low voltage equipment."

  • UVM 10-10 U1

    The technological part of this Plant is placed in a container. There is a provision for an operator place. The capacity in the modes of degassing (nitriding), drying and filtering is at least 6 m3/h, in the mode of heating and filtering — at least 15 m3/h. Power of the band heater is 160, 200, 240 kW (at a Customer’s request). Pressure on the outlet — at least 0,2 MPa.
    Oil parameters after treatment: gas content — not more than 0,1%; mass water content not more than 0,001% (10 g/ton); contamination class — according to GOST17216 not worse than 9 (filtration fineness — 5 µm); mass content of mechanical inclusions — 10 g/ton.

    According to a Customer’s request:
    1. capacity in the heating and filtering mode from 30 to 50 m3/h;
    2. a car with a jacket for warmth-keeping.
  • UVM 10-3 U1

    The technological part of this Plant is placed in a container. There is a provision for an operator place. The capacity in the modes of degassing (nitriding), drying and filtering is at least 3 m3/h, in the mode of heating and filtering — at least 8 m3/h. Power of the band-type heater is 90, 120 kW (at a Customer’s request). Pressure on the outlet — at least 0,2 MPa.
    Oil parameters after treatment are similar to those of plant UVM 10-10 U1.